NPN-compatible wiring

The accessory converts the level indicator's output configuration into a 3-wire NPN-compatible interface (Active Low), simplifying direct integration with the digital input modules of industrial PLCs. 

Thanks to a factory-installed electrical jumper between the 0V DC ground line and the common terminal of the SPDT electromechanical contact, the level indicator provides a 0V DC output signal when the detected material level is reached (default NO configuration). 

 

Key advantages:

  • PLC Compatibility: native 0V DC output signal (Active Low), ideal for standard interfacing with industrial automation systems.

 

Wiring specifications:

  • Required power supply: 24V DC (direct current)
  • Output type: 3-wire NPN, Active Low (0V DC when the signal is active)
  • Default logic: NO (Normally Open) / reversible to NC (Normally Closed)
  • User terminals: +24V DC (power supply), 0V / GND (return), OUT (0V DC signal to PLC)

<p>NPN-compatible wiring</p>

Any questions? Contact us